- Suitable for Maintained or Non-maintained luminaires.
- Electronic charge system
- Deep discharge protection
- Snort-circuit proof battery connection
- Automatic shutdown protection if the LED load is out of range.
- Simple wiring /installation.
- 2 hours or 3hours emergency backup with either Ni-MH battery or Ni-Cd battery
- Provided with a lP20 robust steel iron remote box
- Optional IP65 Waterproof Die-casted Aluminum Box Provided with a LED for indication when battery charge is in process.
- Polarity reversal protection for battery
- Tested in accordance with latest local requirement PPA/104(A) (5th Revision).
E-SOLO
Technical Data
-
Input Rated Voltage
Frequency
220-240VAC 50/60Hz
220-240VDC
-
AC Input Current
50mA
-
AC Input Power Rated
40W max.
-
Power Factor
> 0. 95
-
Charge time
12 hours
-
No-load Power Consumption
3W
-
Output emergency power
Max 12W
-
Output voltage
10…220 V
-
Battery Type
Ni -MH or Ni-Cd battery
-
Battery Accessories
- 9.6V 1.2Ah
- 9.6V 1.6Ah
- 9.6v 2.2Ah
- 9.6v 2.8Ah
- 9.6v 3.6Ah
- 9.6v 4.5Ah
-
Luminaires Type
Maintained or Non Maintained Type refer to wiring diagram
-
Rated duration
2 hours or 3 hours
-
Protection
Short Circuit Protection; Overload Protection;No-load Protection;
-
Environment
Ta/Operation Temperature: 0….+50°C
Ts/Storage Temperature: -25… .+85°C
Tc/Enclosure Temperature: 70°C max.
Humidity: 10%....90%RH
-
Construction
Connection Method: Direct Lead
PRI Wire preparation: 0.5-1.0 sq.mm
-
Dimension
200X39X26mm (L*W*H)
-
MTBF
Switching Testing
>100000 hours
> 10,000 times
-
Life Time
50,000h @50°C(Ta)/ @70°C(Tc)
-
Plug Terminal
JST VHR-2N/3.96mm Plug Terminal for Battery and LED indicator Connection
-
Accessories
Test switch
Status indication LED Light :GREEN-FULLYCHARGED ; RED- CHARGING ; YELLOW.FAULT
-
Safety Standards
CE IEC/EN 61347-1; IEC/EN 61347-2-13; IEC/EN 62384; IEC/EN 61000-3-2; IEC/EN 61000-3-3;IEC/EN61574;EN 55015
-
Housing materials
Zinc Iron
-
Housing Color
White coating